053-1DP00 - Interface modules | Fieldbus slave modules without I/Os

Order no.

053-1DP00

Type IM 053DP
Module ID -

General information

Note -
Features PROFIBUS-DP slave (DP-V0, DP-V1)

For max. 64 peripheral modules

244 Byte input and 244 Byte output data

Technical data power supply

Power supply (rated value) DC 24 V
Power supply (permitted range) DC 20.4...28.8 V
Reverse polarity protection
Current consumption (no-load operation) 90 mA
Current consumption (rated value) 0.95 A
Inrush current 2.8 A
I²t 0.25 A²s
Max. current drain at backplane bus 3 A
Max. current drain load supply 10 A
Power loss 3 W

Status information, alarms, diagnostics

Status display yes
Interrupts yes, parameterizable
Process alarm yes, parameterizable
Diagnostic interrupt yes, parameterizable
Diagnostic functions yes, parameterizable
Diagnostics information read-out possible
Supply voltage display green LED
Service Indicator -
Group error display red LED
Channel error display none

Hardware configuration

Racks, max. 1
Modules per rack, max. 64
Number of digital modules, max. 64
Number of analog modules, max. 64

Communication

Fieldbus PROFIBUS-DP to EN 50170
Type of interface RS485 isolated
Connector Sub-D, 9-pin, female
Topology Linear bus with bus termination at both ends
Electrically isolated
Number of participants, max. 125
Node addresses 1 - 125
Transmission speed, min. 9.6 kbit/s
Transmission speed, max. 12 Mbit/s
Address range inputs, max. 244 Byte
Address range outputs, max. 244 Byte
Number of TxPDOs, max. -
Number of RxPDOs, max. -

Mechanical data

Dimensions (WxHxD) 48.5 mm x 109 mm x 76.5 mm
Weight 155 g

Environmental conditions

Operating temperature 0 °C to 60 °C
Storage temperature -25 °C to 70 °C

Certifications

UL508 certification in preparation