Is it possible to apply modules from VIPA System 200V together with VIPA System 100V?

Yes, the modules from 200V and 100V could be operated together. Herefor the GSD data file from System 100V have to be used.

08/26/2010 Category: System 200V, System 100V

Does SPEED7 supports the Siemens module 6ES7 338-4BC00-0AB0?

Yes, this module could be operated together with VIPA CPUs.

08/26/2010 Category: System 300S / 300V

Are Net-CPUs from VIPA supporting the clock synchronization?

Yes, herefore the Ethernet CP 6GK7 343-1EX21 instead of 6GK7 343-1EX11 has to be configurated.

08/26/2010 Category: System 300S / 300V

Is it possible to update with SD card a VIPA CPU?

No, the SD card does not work with VIPA PLCs. Only MMC and MMC Plus with a capacity of 1GB could be applied.

08/26/2010 Category: General questions

Does VIPA CPUs support PCS7?

Yes, partly possible. The alarm processing is supported. All further functions are not tested.

08/26/2010 Category: General questions